Westermo ODW-730-F2 User Manual

Page 12

Advertising
background image

12

6651-2255

Data transport in multidrop, dual channel, V-mode configuration

RX2

TX2

Device 1

Sending data to

device 3 and 4 on the

primary channel

Device 2

Sending data to
device 5 on the

secondary channel

Device 3

Receiving data from

device 1 on the

primary channel

Device 5

Receiving data from

device 2 on the

secondary channel

TX1

RX1

RX2

TX2

TX1

RX1

RX2

TX2

RS-485

RS-485

RS-485

Fibre

pair

Fibre

pair

Fibre

pair

RS-485

TX1

RX1

RX2

TX2

TX1

RX1

PWR

FP

TD

RD

PWR

FP

TD

RD

PWR

FP

TD

RD

PWR

FP

TD

RD

Device 4

Receiving data from

device 1 on the

primary channel

RS-485

Fibre

pair

RX2

TX2

TX1

RX1

PWR

FP

TD

RD

The first ODW-730 unit recieives data from communications device 1 on the RS-485
port and sends it out on optical fibre TX1 using the primary data channel.
The second ODW-730 unit receives primary channel data on optical fibre RX2. Primary
channel data is repeated out on optical fibre TX1. The second ODW-730 unit also
receives data from communications device 2 on the RS-485 port. The RS-485 data is sent
out on optical fibre TX1 using the secondary data channel.
The third and fourth ODW-730 units receive both primary and secondary channel data
on optical fibre RX2. Both primary and secondary data are repeated out on optical fibre
TX1, but only the primary channel data is sent out on the RS-485 port.
The fifth ODW-730 unit receives both primary and secondary channel data on optical
fibre RX2, but only the secondary channel data is sent out on the RS-485 port.

Advertising