Functional description – Westermo FD-40 User Manual

Page 16

Advertising
background image

16

6630-2242

FD-40 B

Device type

GSD-file

FD-10.GSD

Device type

Slave

Address range

0 to 126

Number of modules

2

Input data

4 word complete consistency

Output data

4 word complete consistency

Data control

One word for serial transfer control

7. Functional description

Technical data

PR

OFIB

US DP data

De

vice

7.1 Buffered, FD-40 B

Functions that are included in the FD-40 B:

1. Send some bytes of data direct to the serial interface

Send up to 6 byte data from PROFIBUS DP to the serial interface

2. Send data to buffer and finally send buffered data to the serial interface

once
Send up to 6 byte PROFIBUS DP data in time to the send buffer. By command can
these buffered data be sent to the serial interface. Up to 15 kbyte can be sent once.

3. Receive buffered data, from serial interface received data

Data received from serial interface will automatically be stored in the receive buffer.
These data will be picked up by PROFIBUS DP, 6 byte each time.

All these three functions are ready to use without any modification by the
configuration tool.
FD-40 can convert PROFIBUS DP data over the serial interface when the unit is in
normal operation mode and the PROFIBUS DP is active, LED CONF inactive and
BA active.