Interface specifications – Westermo LRW-102 User Manual

Page 14

Advertising
background image

14

6650-2260

Interface specifications

Power

Rated voltage

12 to 48 VDC
24 VAC

Operating voltage

10 to 60 VDC
20 to 30 VAC

Rated current

400 mA @ 12 VDC
200 mA @ 24 VDC
100 mA @ 48 VDC

Rated frequency

DC
AC: 48 to 62 Hz

Inrush current I

2

t 0.2

A

2

s

Startup current*

1.0 A

peak

Polarity

Reverse polarity protected

Redundant power input

Yes

Isolation to

TP/FT-10 port and status port

Galvanic connection to

Connection

4-position detachable screw terminal

Connector size

0.2 – 2.5 mm

2

(AWG 24 – 12)

Shielded cable

Not required

* External supply current capability for proper start up.

Status

Port type

Solid state relay

Operating voltage

Up to 60 VDC

Load current

Up to 100 mA

Contact resistance

8 Ω

Isolation to

TP/FT-10 port and power port

Connection

2-position detachable screw terminal

Connector size

0.2 – 2.5 mm

2

(AWG 24 – 12)

TP/FT-10

Electrical specification

L

ON

W

ORKS®

TP/FT-10 using FTT-10A transceiver

Data rate

78.5 kbit/s

Data format

Synchronous

Protocol

LonTalk

®

Transmission range

Up to 2700 m

Termination

Single or double external termination according to TP/FT-10
specification

Isolation to

Power port and status port

Connection

2-positon detachable screw terminal

Connector size

0.2 – 2.5 mm

2

(AWG 24 – 12)

Shielded cable

Not required

Conductive housing

No