Led indicators – Westermo ODW-610-F2 User Manual

Page 16

Advertising
background image

16

6651-22611

LED Indicators

* Time and number of frames are set by DIP-switch S:2.

LED

Status

Description

PWR

Power

ON

In service (power).

Flashing

Fault condition.

OFF

Out of service.

BA

Bus active

ON

PROFIBUS DP in operation.
Received data frame with detected
data rate on the electrical
PROFIBUS DP or optical fibre port.

OFF

Data frame with detected data rate
has not been received, or received
frames have been interrupted during
a time, or a number of consecutive
faulty frames*.

CH 2

Channel

ON

Fibre link at port CH 2 in operation.
Data can be transmitted.

OFF

Fibre link at port CH 2 out of opera-
tion.

CH 1

Channel

ON

Fibre link at port CH 1 in operation.
Data can be transmitted.

OFF

Fibre link at port CH 1 out of opera-
tion.

DPR

Receive PROFIBUS DP

Flash

Receive data on the electrical
PROFIBUS DP port. Data will be
transmitted to the fibre link, if it is a
correct PROFIBUS DP frame.

OFF

FR

Receive fibre link

Flash

Receive data on the Fibre Link.
This frame is transmitted to the
PROFIBUS DP channel.

OFF

FL R

Failure link remote

ON

Remote Fibre Link failure. A fibre link
is out of operation at any other unit
of the optical network.

OFF

All fibre links are in operation at all
other units in the fibre optical net-
work.

FL L

Failure link local

ON

Local fibre link failure. This unit has
identified a fibre link failure.

OFF

Fibre link of this unit is in operation

Advertising