Start up guide

Redundant ring application
Follow the steps below to get the unit up and running in a simple application.

Ring A
Ring B

TX

RX

TX RX

TX

RX

TX RX

TX

RX

TX RX

TX

RX

TX RX

CH 2

CH 1

CH 2

CH 1

CH 2

CH 1

CH 2

CH 1

Master

Slave

Slave

Slave

Prepare the PROFIBUS units
… Configure PROFIBUS DP network, with master and slaves. Check that it is running

correctly with the electrical PROFIBUS DP network.

Prepare the fibre optical network
… Redundant ring. Set switch S2:3 set to ON and all others to OFF, at all units.
… Connect the fibre links between the units.
… Connect the power supply to all units.

• The Fibre links should be in operation, indicated by active CH 1 and CH 2 LED’s.

… Connect each of the PROFIBUS DP slaves to PROFIBUS DP port of corresponding

ODW-610-F2.

… Connect PROFIBUS DP master to PROFIBUS DP port of one ODW-610-F2.

• The PROFIBUS DP will be in operation and the data rate should have been

identified, indicated by BA LED.

… The Redundant ring application is up and running.