Grass Valley 2000NET v3.2.2 User Manual
Page 61
 
2000NET Instruction Manual
61
Service
2.
If only a specific parameter is read-only, the module may be in a mode 
assigning read-only operation to that parameter. Refer to the module’s 
instruction manual.
3.
If only the 2000NET module is read-only, the 2000NET module may be 
in remote lockout mode. 
a.
Check the 2000NET module’s status page to see if the
NET CARD
REMOTE CONTROL
status is disabled.
b.
If so, flip Switch 2 on the S2 DIP switch block (NM CNTRL) to the 
enabled setting (see 
)
.
Event Messages From the Frame Are Not Being Displayed by NetCentral or 
Another SNMP Manager Application
1.
Check that the frame is powered on and configured with an 2000NET 
module on the Network.
2.
Check that the 2000NET module in the frame is loaded with software 
version 2.2.0 or later.
Earlier versions of software do not support SNMP.
3.
Check that the SNMP Agent has been installed and configured on the 
2000NET module. 
View the 2000NET module
CONFIGURATION
page and note the event con-
figuration parameters, the
NET CARD EVENT REPORTS
form and
REPORT
DESTINATIONS
table.
If these are not visible, install the SNMP Agent per the instructions in 
the manual.
4.
Check that the IP Address and Community Name for the SNMP 
Manager has been assigned in the 
REPORT DESTINATIONS
table and is
Active.
•
If there is no entry for the SNMP Manager in the Table, the SNMP 
manager’s IP Address and Community name must be entered (see 
2000NET Configuration Web Page on page 34
).
•
If the entry for the SNMP Manager is incorrect, it must be corrected, 
activated, and the 2000NET module must be rebooted.
•
If the entry has been entered and the Status of the entry is reported
NOT IN SERVICE
, the Active operation for that entry must be selected,
applied and the 2000NET module must be rebooted.
•
If the entry has been entered and the Status of the entry is
NOT READY
,
the entry must be corrected, activated and the 2000NET module 
must be rebooted.
•
If the entry has been entered and the Status of the entry is
ACTIVE
–PENDING REBOOT
, the 2000NET module must be rebooted.