Causes of minor error messages, Operating parameters erased, Limit switch <axis – HEIDENHAIN TNC 415 (259 9x0) Service Manual User Manual
Page 8: Plc program not translated, Positioning error, Power interrupted, 1 causes of minor error messages

SERVICE MANUAL TNC 415B/425
Page 5
Issue: 20.08.95
2.1 Causes of Minor Error Messages
OPERATING PARAMETERS ERASED
-
With new and exchange controls, the machine parameters are always erased
-
Defective buffer batteries, accumulator or capacitor
-
RAM error on the processor board
-
Software exchanged
LIMIT SWITCH <AXIS>
-
"Manual" Operating Mode
The preset software limit switch has been reached during traverse with the axis address keys.
-
"Automatic" Operating Mode
The calculated position of the current block is beyond the software limit switch range or beyond the
additional limit (set with the MOD function <AXIS LIMIT>). The positioning is not performed.
Machine Parameters for the Software Limit Switches
X+
X-
Y+
Y-
Z+
Z-
Default setting
Activation via PLC
1)
Activation via PLC
1)
IV+
IV-
V+
V-
Default setting
Activation via PLC
1)
Activation via PLC
1)
1)
PLC markers M 2816 and M 2817
POWER INTERRUPTED
-
After a reset signal of the power supply (e.g. line voltage drops)
-
Important machine parameters may have been changed:
e.g. MP 210, MP 410.3, MP 730, MP 3240.1, MP 7210, MP 7310
POSITIONING ERROR
-
The servo lag monitor set in the machine parameters 1410.X or 1710.X has responded.
(Check the run-in behaviour of the axis; readjust, if necessary.)
PLC PROGRAM NOT TRANSLATED
- After editing, the PLC program must be compiled (translated) anew.