5  Troubleshooting

SMA America, LLC

22

SB6-11TLUS-BA-eng-BUS121211

User Manual

Goes out briefly
once per second

Derating
At temperatures above +113°F (+45°C), the
inverter continues to operate but reduces the
power so as to protect the internal
components from overheating.
Corrective measures:

• Ensure that the inverter has sufficient

ventilation.

• Ensure that air can emerge from the fan

guards at the bottom of the inverter. If air
is not emerging from the fan guards,
clean the fan guards
(see Section 6.4).

B

Red LED

Glowing

Ground fault
A ground fault is present in the PV array. The
inverter does not feed into the power
distribution grid.
Corrective measures:

• Contact installer.

Position

Description

Status

Explanation