5  Troubleshooting

User Manual

SB6-11TLUS-BA-eng-BUS121211

33

VacL1-Bfr
VacL2-Bfr,
VacL1-Srr
VacL2-Srr

The DC input voltage is too high or too low on the indicated branch.
The inverter disconnects from the power distribution grid. As soon as the
error has been remedied, the inverter tries to feed into the power
distribution grid again. If the inverter cannot feed into the power
distribution grid after several attempts, the inverter trips the permanent
operation inhibition.
Corrective measures:

• Contact installer.

VdclinkMax

The internal hardware monitoring system has detected an overvoltage in
the intermediate circuit of the inverter.
The inverter disconnects from the power distribution grid. As soon as the
error has been remedied, the inverter tries to feed into the power
distribution grid again. If the inverter cannot feed into the power
distribution grid after several attempts, the inverter trips the permanent
operation inhibition.
Corrective measures:

• Contact installer.

VpvMax

The DC input voltage is above the set maximum limiting value.
The inverter disconnects from the power distribution grid. As soon as the
error has been remedied, the inverter tries to feed into the power
distribution grid again. If the inverter cannot feed into the power
distribution grid after several attempts, the inverter trips the permanent
operation inhibition.
Corrective measures:

• Turn the rotary switch of the DC Disconnect to the Off position

immediately.

• Contact installer.

Watchdog
Watchdog Srr

The inverter has detected an internal program run disturbance.
The inverter disconnects from the power distribution grid. As soon as the
error has been remedied, the inverter tries to feed into the power
distribution grid again. If the inverter cannot feed into the power
distribution grid after several attempts, the inverter triggers the permanent
operation inhibition.
Corrective measures:

• Contact installer.