3  Power-Generating Unit Protection Test

Instructions for the Protection Test of the Power-Generating Unit

SCCPXT_EZE-SG-en-11

11

3.3 Test Parameters

3.3.1 Overview of Test Parameters

The inverters have two relevant parameter pairs each for voltage increase protection and voltage drop protection and

one relevant pair of parameters for frequency increase protection and frequency drop protection.

3.3.2 Saving the Test Parameters

Procedure:

1. Log into the user interface.
2. Select PV system > Devices.
3. Select

.

☑ A list of the available device types appears.

4. Select the desired device type.

☑ A list appears containing all available devices of this type.

5. Select the desired device from the list.
6. Select the tab Parameters.
7. Save the test parameter values.

Voltage increase protection

1st level: V> / t

V>

2nd level: V>> / t

V>>

Setting value / operating time

VCtlhLim / VCtlhLimTm

VCtlhhLim / VCtlhhLimTm

Voltage drop protection

1st level: V< / t

V<

V<< / t

V<<

Setting value / operating time

VCtllLim / VCtllLimTm

VCtlllLim / VCtlllLimTm

Frequency increase protection

1st level: f> / t

V>

Setting value / operating time

HzCtlhLim / HzCtlhLimTm

Frequency drop protection

1st level: f< / t

V<

Setting value / operating time

HzCtllLim / HzCtllLimTm

Access to parameters
The parameters needed for the power-generating unit protection test are only accessible after the installer password

has been entered. The installer password is changed during the initial installation. You can get the changed installer

password from the PV system operator. The default password can be found in the operating manual.