Parameters and Error Messages

SMA Solar Technology AG

36

Erdung_HF-IXX105020

Installation Guide

Parameter "Module grounding prescribed?" / "MdGndMdt"
Configuration: No

Cause Correction

• Event number 35
• Display message

< Insulation resist. - check generator >

• Red LED glows continuously.
• Green LED glows continuously.
• The inverter feeds into the grid.

An overcurrent has occurred.

• Correct the error as described in

section .6.3.3 ”Correct Insulation
Error” (page 38).

• Event number 35
• Display message

< Insulation resist. - check generator >

• Red LED glows continuously.
• Green LED glows continuously.
• The inverter feeds into the grid.

An insulation fault has occurred.

• Correct the error as described in

section 6.3.3 ”Correct Insulation Error”
(page 38).

• Event number 42
• Display message

< Wrong earthing type; check earthing set >

• Red LED glows continuously.
• Green LED glows continuously.
• The inverter feeds into the grid.

The SMA Plug-in Grounding has been
connected incorrectly (reverse polarity) or is
missing.

• Correct the error as described in

section 6.3.4 ”Correct the Grounding
Type” (page 38).