Rating for a line circuit breaker in a photovoltaic electrical power unit
operated in parallel with the low-voltage grid

Various factors should be taken into account when selecting line circuit breakers. These
include, for example:
•

The type of cable used (conductor material and insulation)

•

Ambient temperatures affect the cables (higher temperatures result in a reduced
maximum current load)

•

Method of routing the cable (reduces the ampacity of the conductor)

•

Bundling cables together (reduces the ampacity of the conductor)

•

Loop impedance [Z] (in the event of a body contact this limits the current that can
flow and therefore determines the response behavior of the circuit breaker)

•

Sufficient distance between the circuit breakers so as to avoid undue heating (heat
can trigger the circuit breakers early).

•

Selectivity

•

Protection class of the connected load (VDE 0100, part 410, Protection against
electric shock)

The following standards should be followed in all cases:
•

DIN VDE 0298-4

(Cable routing and current-carrying capacity)

•

DIN VDE 0100; part 430 (Protective measures; protection of cable and cords

against overcurrent)

•

DIN VDE 0100; part 410 (Protective measures; protection against electric

shock)

Attention!
We recommend using a 16 A line circuit
breaker to protect the power circuit. No
loads should be connected to this power
circuit.

Please pay attention to chapter 11 "Rating for a line circuit breaker" (Page 51).