3 country-specific parameter settings, Country-specific parameter settings – SMA SB 1100LV User Manual
Page 42

Technical data
SMA
Technologie AG
Page 42
SB1100LV-11:SE2006
Installation Guide
8.4.3 Country-specific parameter settings
The parameters listed below represent country-specific settings and are only displayed
in installer mode. All other parameters are international and can be viewed in the table
in chapter 8.4.2.
Parameters designated with * are safety-related grid monitoring parameters. To
change the SMA grid guard parameters, you must enter you personal SMA grid
guard password (Inst.-Code). Please call the Sunny Boy Hotline to obtain your
personal SMA grid guard password.
Name
Unit
Country settings
Germany
Great Britain
Spain
Default
GER/
VDE0126-1-1
GB/G83
SP/RD1663
dFac-Max
Hz/s
0.25
0.2
2
dZac-Max
mOhm
750
350
350
Fac-delta-
Hz
2.45
0.5
0.98
Fac-delta+
Hz
0.19
0.5
0.98
I-Ni-Test
mA
6000
0
0
T-Start
s
10
180
10
Uac-Min
V
198
209
199
Uac-Max
V
260
261
250