11 Rating for a line circuit breaker

Required technical information for the inverters used

•

Maximum output current = 5 A

•

Maximum permissible fuse protection for the inverter = 16 A

The choice of cable together with the way it is routed, ambient temperatures and other
underlying conditions limit the maximum fuse protection for the cable.
•

In our example we assume that the chosen cable (2.5 mm²) is ideally routed and
can take a nominal current of 11 A.

Selecting a line circuit breaker:

•

The maximum possible nominal current for the cable used and the maximum
possible fuse protection for the inverter now limit the maximum possible nominal
current for the line circuit breaker.

•

In our example, 10 A is possible.

However, the thermal suitability of the line circuit breaker still needs to be checked.

Example for the thermal rating for a line circuit breaker in a photovoltaic electrical
power unit operated in parallel with the low-voltage grid.
We assume a PV system with 9 Sunny Boy SB 1100LV inverters, with three
inverters per phase.