SMA SMC 7000HV Installation User Manual
Page 72

Troubleshooting
SMA Solar Technology AG
72
SMC70HV11-IA-IEN112970
Installation Manual
Zac-Bfr
Zac-Srr
The grid impedance has left the permissible range. The suffixes "Bfr" und
"Srr" are not relevant.
The inverter disconnects itself from the public grid for safety reasons. The
impedance is calculated from both the grid impedance and the
impedance of the AC cable of the inverter.
Corrective measures
• Check the grid impedance and grid connection on the inverter.
• Use an AC cable with an adequate cross-sectional area
(= low impedance) as described in section 5.2 "Connection to the
Power Distribution Grid (AC)" (page 24). If required, re-tighten the
screws on the AC terminals.
• If this fault recurs, contact the SMA Serviceline.
Message
Description and corrective measure