Technical Data
SMA Solar Technology AG
82
SMC70HV11-IA-IEN112970
Installation Manual
*EN 50438: Does not apply to all national standard deviations.
VDE-AR-N-4105-HP: Valid from firmware version 2.10. Setting in accordance with VDE-AR-N-4105 (Germany) for PV plants
> 13.8 kVA
.
Climatic conditions in accordance with IEC 60721-3-4, installation type C,
class 4K4H
Climatic conditions in accordance with IEC 60721-3-4, transport type E, class 2K3
Features
Country standards, as of 07/2011*
VDE 0126-1-1
VDE-AR-N-4105
AS4777
C10/11
PPDS
GBT19939-2005
CGC GF001-2009
UTE C15-712-1
PPC
DK 5940
EN 50438
RD 1663/2000
RD 661/2007
IEC 61727 PEA
G83/1-1
G 59/2
Extended temperature range
− 25°C … +60°C
Extended humidity range
0% … 100%
Extended air pressure range
79.5 kPa … 106 kPa
Temperature range
− 25°C … +70°C
DC connection
SUNCLIX DC connector
AC connection
Spring terminal
Display
LC text display
Bluetooth
®
Wireless Technology
optional
RS485, galvanically isolated
optional