3 connecting additional earthing, Connecting additional earthing – SMA WB 3300-11 Installation User Manual

Page 28

Advertising
background image

Electrical Connection

SMA Solar Technology AG

28

WB33-38-IA-IEN120940

Installation Manual

5.3.3 Connecting Additional Earthing

If a second protective conductor, additional earthing or equipotential bonding is required, you can
also earth the inverter on the enclosure.

Overview of additional earthing

Procedure

1. Disconnect the inverter on the AC and DC side as described in Section 7.2 "Opening the

Inverter" (page 48).

2. Align washer, terminal lug with protective

conductor and conical spring washer on cheese-
head screw. The teeth of the conical spring washer
must be facing the metal bracket.

3. Insert the cheese-head screw into the metal bracket

and tighten to a torque of 6 Nm.

4. Check that the contact between the protective conductor and the enclosure is in accordance

with the regulations valid in the country of installation.

Object

Description

A

Metal bracket on the bottom of the inverter enclosure

B

Conical spring washer (included in delivery)

C

Terminal lug (M6) with protective conductor

D

Washer

E

M6x12 cheese-head screw (included in delivery)