7.3 Closing the Inverter

1. Attach the enclosure lid using the 4 screws and the

conical spring washers with the toothing facing
toward the enclosure lid. The screws must be
tightened with approximately 6 Nm torque to
ensure that the enclosure is sealed and the lid
properly earthed.

2. Check the DC connectors for correct polarity and plug them in.

To release the DC connectors see Section 7.2 "Opening the Inverter" (page 48).
☑ The DC connectors click audibly into position. To release the DC connectors,

see Section 7.2 "Opening the Inverter" (page 48).

3. Close all unused DC inputs as described in Section 5.5.4 "Connecting the Small Wind Turbine

System (DC)" (page 34) to ensure that the inverter is properly sealed.

4. Ensure that all DC connectors are securely in place.

DANGER!
Danger to life due to live enclosure lid

The earthing of the lid is effected by the conical spring washers.

• Attach the conical spring washers for all screws with the toothing facing toward the

enclosure lid.