SMA WB 3300-11 Installation User Manual

Page 63

Advertising
background image

SMA Solar Technology AG

Troubleshooting

Installation Manual

WB33-38-IA-IEN120940

63

3. Release and disconnect all DC connectors. To do

this, insert a flat-blade screwdriver
(blade width: 3.5 mm) into one of the side slots and
pull the DC plug connectors out. Take care
NOT TO PULL ON THE CABLE
.

4. Remove the AC connection socket from the inverter.

5. Disconnect L1, L2 and L3 of the small wind turbine system from the Windy Boy Protection Box.
6. Measure the resistance between the phases of the small wind turbine system and the earth

potential:
– Measure the resistance between L1 of the small wind turbine system and the earth potential.
– Measure the resistance between L2 of the small wind turbine system and the earth potential.
– Measure the resistance between L3 of the small wind turbine system and the earth potential.

Result

What to do

The measured resistance is virtually infinite.

☑ There is no earth fault in the small wind

turbine system.

There is probably an earth fault in the
Windy Boy Protection Box or in the supply
cables to the inverter.

• Disconnect the Windy Boy Protection Box

from the inverter and measure the
resistance of all connections and the earth
potential.