7 Configuring DeviceNet Messaging

YASKAWA ELECTRIC

SIEP C730600 43B 1000-Series Option SI-N3 Technical Manual

21

7

Configuring DeviceNet Messaging

This section provides information on the methods used to control the drive on DeviceNet.

‹

Drive Configuration on DeviceNet

„

Polled Configuration

Configure the drive DeviceNet polled connection before receiving commands from a master device. The two parameters
that must be configured are:

• F6-52: Polled Consuming Assembly (PCA)

Note: Output assembly consumed by the drive.

• F6-53: Polled Producing Assembly (PPA)

Note: Input assembly produced by the drive.

The default connection paths for the option are set for Extended Speed Control.

The PCA and PPA parameters can be accessed by two methods:

• A software configuration tool (not supplied), and Yaskawa Electronic Data Sheet (EDS)

Note: The PCA and PPA parameters can be accessed from the “DN: Polled Config” parameter group.

• A software configuration tool (not supplied), via a DeviceNet message path, such as Extended Speed Control

Note: Use DeviceNet Connection Object to change the PCA or PPA if required by the application (Class 5, Instance 1, Attributes 14

and 16)

One of each PCA and PPA assembly from the following table must be selected to configure the drive for polled
operation.

Table 7 Supported Polled Assemblies (PCA and PPA)

Assembly

Number

(decimal)

Description

Type Bytes Page

20

Basic Speed Control Output - 20 (0x14)

PCA

4

23

21

Extended Speed Control Output - 21 (0x15)

(Default Setting)

PCA

4

23

22

Speed and Torque Control Output - 22 (0x16)

PCA

6

24

23

Extended Speed and Torque Control Output - 23 (0x17)

PCA

6

24

70

Basic Speed Control Input - 70 (0x46)

PPA

4

40

71

Extended Speed Control Input - 71 (0x47)

(Default Setting)

PPA

4

40

72

Speed and Torque Control Input - 72 (0x48)

PPA

6

41

73

Extended Speed and Torque Control Input - 73 (0x49)

PPA

6

42

100

MEMOBUS/Modbus Message Command (Vendor Specific Yaskawa Electric (YE) Assy) - 100
(0x64)

PCA

5

25

101

Standard Control (Vendor Specific Yaskawa Electric (YE) Assy) - 101 (0x65)

PCA

8

26

102

Accel/Decel Time (Vendor Specific Yaskawa Electric (YE) Assy) - 102 (0x66)

PCA

8

27

105

Enhanced Speed Control, Dynamic (Vendor Specific Yaskawa Electric (YE) Assy) - 105 (0x69)

PCA

8

28

106

Enhanced Control (Vendor Specific Yaskawa Electric (YE) Assy) - 106 (0x6A)

PCA

8

30

107

Standard DI/DO Control (Vendor Specific Yaskawa Electric (YE) Assy) - 107 (0x6B)

PCA

8

31

108

Enhanced Torque Control, Dynamic (Vendor Specific Yaskawa Electric (YE) Assy) - 108 (0x6C)

PCA

8

32

120

Speed Command 1 (Vendor Specific Yaskawa Electric (YE) Assy) - 120 (0x78)

PCA

4

33

121

Torque Command 1 (Vendor Specific Yaskawa Electric (YE) Assy) - 121 (0x79)

PCA

4

34

122

Speed Command 2 (Vendor Specific Yaskawa Electric (YE) Assy) - 122 (0x7A)

PCA

6

35

123

Torque Command 2 (Vendor Specific Yaskawa Electric (YE) Assy) - 123 (0x7B)

PCA

6

36

124

Speed Dynamic Assy (Vendor Specific Yaskawa Electric (YE) Assy) - 124 (0x7C)

PCA

8

37

125

Torque Dynamic Assy (Vendor Specific Yaskawa Electric (YE) Assy) - 125 (0x7D)

PCA

8

38

126

Speed/Torque Assy (Vendor Specific Yaskawa Electric (YE) Assy) - 126 (0x7E)

PCA

8

39

130

Speed Status (Vendor Specific Yaskawa Electric (YE) Assy) - 130 (0x82)

PPA

4

43

131

Current Status (Vendor Specific Yaskawa Electric (YE) Assy) - 131 (0x83)

PPA

4

44

132

Current & Speed Status (Vendor Specific Yaskawa Electric (YE) Assy) - 132 (0x84)

PPA

6

45