5 Installation Procedure

20

YASKAWA TOEP YEAOPT 07 A1000 Option DI-101 120 Vac Interface Installation Manual

Wire Gauges, Tightening Torques, and Crimp Terminals

Wire Gauges and Tightening Torques

Wire gauge and torque specifications are listed in

Table 3

.

Table 3 Wire Gauges and Tightening Torques

Crimp Terminals

Yaskawa recommends using CRIMPFOX 6 by Phoenix Contact or equivalent crimp

terminals with the specifications listed in

Table 4

for simplier and more reliable wiring.

Table 4 Crimp Terminal Sizes

Terminal

signal

Screw

Size

Tightening

Torque

N.m (in.lb)

Bare Cable

Crimp Terminals

Wire

Type

Applicable

Gauges mm

2

Recomm.

Gauge mm

2

Applicable

Gauges mm

2

Recomm.

Gauge mm

2

S1 to S8
and X2

M2

0.22 to 0.25

(1.95 to 2.21)

Stranded wire:

0.25 to 1.0

(24 to 17 AWG)

Solid wire:

0.25 to 1.5

(24 to 16 AWG)

0.75

(18 AWG)

0.25 to 0.5

(24 to 20 AWG)

0.5

(20 AWG)

Stranded

or solid

wire

Wire Gauge

mm

2

Phoenix Contact

Model

L

mm (in)

d1

mm (in)

d2

mm (in)

0.25 (24 AWG)

AI 0.25 - 6YE

10.5 (13/32)

0.8 (1/32)

2 (5/64)

0.34 (22 AWG)

AI 0.34 - 6TQ

10.5 (13/32)

0.8 (1/32)

2 (5/64)

0.5 (20 AWG)

AI 0.5 - 6WH

14 (9/16)

1.1 (3/64)

2.5 (3/32)

d1

d2

6 mm

L

Advertising