DWG. NO. 02Y00025-0350
SHEET NO. 6 OF 6
R E L . 0 5 / 0 5 / 9 3
( m - df )
Refer to Sheet 1 for latest change.
Table 6 Function of DO-08 Coded Output From GPD 503, GPD 575 or VCD 703
Bits 3, 2, 1, 0
Output Contents
Bits 3, 2, 1, 0
Output Contents
0 0 0 0
No fault
1 0 0 0
External fault (EFxx)
0 0 0 1
Overcurrent (oC)
1 0 0 1
Drive hardware fault (CPFxx)
(including grounding)
1 0 1 0
Motor overload (oL1)
0 0 1 0
Overvoltage (ou)
1 0 1 1
not used
0 0 1 1
Drive overload (oL2)
1 1 0 0
Power loss (Uu) (including
0 1 0 0
Drive overheat (oH2)
momentary power loss)
0 1 0 1
not used
1 1 0 1
not used
0 1 1 0
Fuse blown (FU)
1 1 1 0
not used
0 1 1 1
not used
1 1 1 1
Cooling fan fault (FAn)
7. Reinstall and secure drive cover.
8. Place this instruction sheet with the drive’s technical manual.
THIS COMPLETES INSTALLATION OF THIS OPTION.