4.3 Modified Parameters and Functions

Parameter

Number

Description

A1-02

Motor 1 Control Method: Setting fixed to ‘0’ (Open Loop V/F)

B3-01

Speed Search Selection: Range changed to 2 ~ 3

B5-15

PID Sleep Level: 1000.0Hz maximum

B6-01

Dwell Frequency at Start: 1000.0Hz maximum *1

B6-03

Dwell Frequency at Stop: 1000.0Hz maximum *1

C1-11

Acc/Dec Switch Frequency: 1000.0Hz maximum *1

C4-01

Torque Compensation Gain: Default changed to 0.0

C6-03

Carrier Frequency Upper Limit: 10.0kHz maximum and default

C6-04

Carrier Frequency Lower Limit: 10.0kHz maximum and default

D1 Group

Frequency References: 1000.0Hz maximum *1

D3-01

Jump Frequency 1: 1000.0Hz maximum *1

D3-02

Jump Frequency 2: 1000.0Hz maximum *1

D3-03

Jump Frequency 3: 1000.0Hz maximum *1

D6-02

Field Weakening Frequency: 1000.0Hz maximum *1

E1-04

Motor 1Maximum Output Frequency: 1000.0Hz maximum *1

E1-06

Motor 1 Base Frequency: 1000.0Hz maximum *1

E1-07

Motor 1 Midpoint Frequency A: 1000.0Hz maximum *1

E1-09

Motor 1 Minimum Frequency: 1000.0Hz maximum *1

E1-11

Motor 1 Midpoint Frequency B: 1000.0Hz maximum *1

E3-01

Motor 2 Control Method: Range fixed to 0 (Open Loop V/F)

E3-02

Motor 2 Maximum Output Frequency: 1000.0Hz maximum *1

E3-04

Motor 2 Base Frequency: 1000.0Hz maximum *1

E3-05

Motor 2 Midpoint Frequency A: 1000.0Hz maximum *1

E3-07

Motor 2 Minimum Frequency: 1000.0Hz maximum *1

F3-01

DI-08 / DI-16H2 Selection: Range changed to 0 ~ 4, 7

L4-01

Speed Agree Level: 1000.0Hz max *1

L4-03

Speed Agree Level +/-: -1000 to 1000Hz max *1

N1-01

Hunting Prevention Selection: Default changed to 0 (Disabled)

O1-03

Keypad Display Scaling: Setting ‘0’ resolution changed to 0.1Hz

*1: 1500Hz when C6-11 = 1 (Frequency Reference Limit).

Advertising