Connect to the

LonWorks

network.

„

Connect the network to the

L

ON

W

ORKS

Option Card

as shown.

‰

Network Identification and Node Configuration
The

L

ON

W

ORKS

Option Card

is shipped unconfigured. This implies that the application is loaded and communications parameters are defined but the

option has not been installed on the network. On power up, an un-configured node can be recognized by the SERVICE LED blinking at 2Hz.
Network identification is accomplished with an installation tool. Unique network identities are established by pairing “logical” addresses with a device’s

48-bit Neuron ID.
„

SERVICE Button

Each option card has a Service Button. If using a configuration tool utilizing this feature, press the Service Button when prompted to do so. When

pressed, a broadcast message is sent which contains the Neuron ID and program ID. This uniquely identifies the node on the network. This method

works best for small networks or with portable installation tools.

„

Find and Wink

When it is impractical to press each node’s Service Button for installation (e.g. in large networks or a node is physically enclosed), the “find and

wink” installation method is useful. With this method, the installation tool queries the network for all unconfigured nodes. Nodes respond with their

Neuron ID and a logical address is assigned. A “wink” command can then be sent to each logical address. In response to this command, the

TRANSMIT

and RECEIVE LED’s will blink rapidly for several seconds. In this manner, the exact physical location of each node can be identified.

„

Reclaiming a Node

ƒ

A node can be “reclaimed”, or returned to its unconfigured state, as follows:

ƒ

Remove power from the drive and wait for the charge lamp to be completely extinguished.

ƒ

Press and hold the Service Button.

ƒ

Re-apply drive power, continuing to press and hold the Service Button.

ƒ

After approximately 5 seconds, the SERVICE LED should begin flashing at a 0.5 Hz rate, indicating the unconfigured state. This procedure

sets both domain table entries to “undefined” and sets the channel ID to 0.

‰

LED Status Indicators and Diagnostics

LED Display

Condition

Solution

PWR Receive Transmit Fault

Service

BLINK

0.5Hz

Option is Not Configured

• Configure Option

FLASH

1sON_2sOFF_ContON

Application missing

• Download application image file

• Assign network Identity

OFF OFF OFF OFF

OFF

Power

not

supplied

• Check that drive has power

• Check option card seating in CN2 connector

ON BLINK BLINK BLINK

OFF

Communications not

established

• Check drive parameters (refer to table above)

• Check connection between option and drive

ON

ON

OFF

Communications

Loss • Check network cable connections

ON

FLASH

OFF

OFF

Normal communications

Flash each time serial task is complete

Approximately 0.5Hz when drive is at STOP

Approximately 1.0Hz when drive RUN is active

ON

FLASH

OFF

OFF

Normal

communications

Flash for every 5 network variables updates

N
E

T
A

N
E

T
B

1

2

3

4

5

6

7

8

RJ45 Socket