E7, f7 or p7 ac drive, Gpd 506/p5 ac drive, G7 ac drive – Yaskawa AI-010 User Manual

Page 3

Advertising
background image

Yaskawa Electric America, Inc – www.drives.com

IG.AFD.50, Page 3 of 5

Date: 05/22/2007, Rev: 07-05

3-15PSI Pressure Transducer Option Card

AI-010

soldering. The (2) terminals “+V” and “AC” on the card are connected to the same (2) fingers on the card, and are
provided for customer connections.

12. Route the tubing the best way to the barb fitting, cut off any excess length and press onto the barb. If the tubing is already

pressed onto the barb, use a knife to place a sideways slit into the tubing, at the barb to remove it. Then cut the tubing to
desired length and press onto barb.

13. Connect the 3-15PSI pneumatic signal to the adapter on the outside of the drive enclosure. Apply the maximum pressure

(20PSI) to the hose to verify its proper installation and detect any leakage or breakage. After this test, lower the pressure
down to minimum (less than 2PSI) or zero.



E7, F7 or P7 AC Drive





GPD 506/P5 AC Drive




























Terminal No: A2
4 - 20mA
Auto Mode FREQ. REF. Input

Terminal No: AC
Analog Common

Terminal No: FC
Analog Common

Terminal No: FS
+15VDC

Terminal No: +V
+15VDC

Terminal No: FI
(With n043 =1) 4 - 20mA Auto
Mode FREQ. REF. Input

Close up of Pressure Sensor Card

(UTC000038)

G7 AC Drive

Terminal No: +V
+15VDC

AC

Terminal No: A2
4 - 20mA

Terminal No:

Analog Common

Auto Mode FREQ. REF. Input

Figure 3. Installation of Pressure Sensor Card onto Drive Control Board of

GPD506/P5, E7, F7, P7, and G7 Drives