3-15PSI Pressure Transducer Option Card
AI-010
soldering. The (2) terminals “+V” and “AC” on the card are connected to the same (2) fingers on the card, and are
provided for customer connections.
12. Route the tubing the best way to the barb fitting, cut off any excess length and press onto the barb. If the tubing is already
pressed onto the barb, use a knife to place a sideways slit into the tubing, at the barb to remove it. Then cut the tubing to
desired length and press onto barb.
13. Connect the 3-15PSI pneumatic signal to the adapter on the outside of the drive enclosure. Apply the maximum pressure
(20PSI) to the hose to verify its proper installation and detect any leakage or breakage. After this test, lower the pressure
down to minimum (less than 2PSI) or zero.
E7, F7 or P7 AC Drive
GPD 506/P5 AC Drive
Terminal No: A2
4 - 20mA
Auto Mode FREQ. REF. Input
Terminal No: AC
Analog Common
Terminal No: FC
Analog Common
Terminal No: FS
+15VDC
Terminal No: +V
+15VDC
Terminal No: FI
(With n043 =1) 4 - 20mA Auto
Mode FREQ. REF. Input
Close up of Pressure Sensor Card
(UTC000038)
G7 AC Drive
Terminal No: +V
+15VDC
AC
Terminal No: A2
4 - 20mA
Terminal No:
Analog Common
Auto Mode FREQ. REF. Input
Figure 3. Installation of Pressure Sensor Card onto Drive Control Board of
GPD506/P5, E7, F7, P7, and G7 Drives