Digital Output Option Card

DO-02C

Table 4. DO-02C Output Selection

Control Mode (A1-02)

F5-01

and

F5-02

Setting

Function

0: V/F

1: V/F PG

2: OLV

3: F

V

4: OLV2

(1

)

0

During Run 1
(ON: Run command with voltage output. Includes Decel and DC injection)

X

X

X

X

X

1

Zero Speed (ON: Fout < E1-09)

X

X

X

X

X

2

Fref/Fout Agree 1 (ON: Fref = Fout, detection width L4-02)

X

X

X

X

X

3

Fref/L4-01 Agree 1 (ON: Fref = Fout = ±L4-01, detection width L4-02)

X

X

X

X

X

4

Frequency Detection 1 (ON: +L4-01

≥ Fout ≥ - L4-01, detection width L4-02)

X

X

X

X

X

5

Frequency Detection 2 (ON: Fout

≥ +L4-01 or Fout ≤ -L4-01, detection width L4-02)

X

X

X

X

X

6

Inverter Ready (ON: No fault and not in programming mode)

X

X

X

X

X

7

DC Bus Undervoltage (UV1, UV2)
(ON: DC bus below L2-05 or loss of pre-charge contactor answerback)

X

X

X

X

X

8

Baseblock 1 N.O. (ON: Baseblock function is active)

X

X

X

X

X

9

Operator Reference (ON: Frequency reference source is from operator)

X

X

X

X

X

A

Local/Remote Operation (ON: Start/stop source is from operator)

X

X

X

X

X

B

Torque Detection 1 N.O. (ON: Current is greater/lower than L6-02 for L6-03 time)

X

X

X

X

X

C

Loss of Frequency Reference (Function enabled when L4-05 = 1)

X

X

X

X

X

D

Braking Resistor Fault (ON: Resistor overheat or braking transistor fault)

X

X

X

X

X

E

Fault (ON: Fault occurred other than CPF00 and CPF01)

X

X

X

X

X

F

Not Used (Set for use as remote I/O when drive has network communication link)

X

X

X

X

X

10

Alarm (ON: Alarm occurring)

X

X

X

X

X

11

Fault Reset Command Active (keypad, terminal, network)

X

X

X

X

X

12

Timer Function Output (See parameter group B4)

X

X

X

X

X

13

Fref/Fout Agree 2 (detection width L4-04)

X

X

X

X

X

14

Fref/Fout Agree 2 (ON: Fref = Fout = L4-03, detection width L4-04)

X

X

X

X

X

15

Frequency Detection 3 (ON: Fout

≤ L4-03, detection width L4-04)

X

X

X

X

X

16

Frequency Detection 4 (ON: Fout

≥ L4-03, detection width L4-04)

X

X

X

X

X

17

Torque Detection 1 N.C. (OFF: Current is greater/lower than L6-02 for L6-03 time)

X

X

X

X

X

18

Torque Detection 2 N.O. (OFF: Current is greater/lower than L6-05 for L6-06 time)

X

X

X

X

X

19

Torque Detection 2 N.C. (OFF: Current is greater/lower than L6-05 for L6-06 time)

X

X

X

X

X

1A

Reverse Direction (ON: Motor rotation is in reverse due to run command or Fref)

X

X

X

X

X

1B

Baseblock 2 N.C. (OFF: Baseblock function is active)

X

X

X

X

X

1C

Motor 2 Selection
(ON: Motor 2 selected using a digital input (H1-XX) programmed for “16”)

X

X

X

X

X

1D

Regenerative operation (ON: During regenerative operation.)

-

-

-

X

X

1E

Automatic Fault Restart (ON: Automatic fault restart function is active. See L5-01)

X

X

X

X

X

1F

Motor Overload OL1 Alarm (ON: 90% or greater OL1 detection level)

X

X

X

X

X

20

OH Alarm (ON: Heatsink temperature is greater than L8-02)

X

X

X

X

X

30

Torque Limit (ON: Torque limit function active)

-

-

X

X

X

31

Speed Limit During Speed Control (ON: Speed limit function active)

-

-

-

X

X

32

(2)

Speed Limit During Torque Control (ON: Speed limit function active)

-

-

-

X

X

33

Zero Servo Complete (ON: Zero servo function is within the b9-02 detection width)

-

-

-

X

-

37

During Run 2 (ON: Run command with voltage output. Does not include baseblock,
DC injection, or initial excitation)

X

X

X

X

X

38

(2)

Drive Enable
(ON: Drive Enable selected using a digital input (H1-XX) programmed for “6A”)

X

X

X

X

X

(1) Available in the G7 only.
(2) Not available in the GPD515/G5.