Safety Circuit Installation

On power up, the E7 Electronic Bypass will display a red "Safety Open" LED in the System Status area of the front
control panel if a normally closed (N.C) safety circuit is not been installed between TB1-1 and TB1-9 on PCB A2. This
condition will prevent Drive or Bypass operation.

Figure 1

Figure 1 Safety Open LED Indication

„

Installing or Deactivating the Safety Circuit

One of these three actions below must be taken prior to equipment start-up to prevent the Safety Open condition.

1. Option 1: Install a N.C. Safety Circuit between TB1-1 and TB1-9 on PCB A2 according to

Figure 2

.

2. Option 2: Install a jumper between TB1-1 and TB1-9 on PCB A2 according to

Figure 3

. This method should be used if

a Safety Circuit will be added later in the installation

.

3. Option 3: De-activate these terminals by moving DIP switch S2-7 to the ON position (toward the enclosure door)

according to

Figure 4

. This solution is only suggested if a Safety Circuit will never be applied to the drive system

.

Figure 2

Figure 2 Option1: Normally Closed (N.C.) Safety Circuit Installation