1 Supplemental Safety Information - E7 Electronic Bypass

6

IG.E7.05 Yaskawa AC Drive - E7 Electronic Bypass Manual Supplement

‹

Damper/BAS Interlock Circuit Installation

When a Run command is received in HAND or AUTO mode, the E7 Electronic Bypass will display a red "Damper/BAS"
LED in the System Status area of the front control panel. This condition will prevent Drive or Bypass operation.

Figure 5

Figure 5 Damper BAS Interlock LED Indication

„

Installing or Deactivating the Damper/BAS Interlock Circuit

One of these three actions below must be taken prior to equipment start-up to prevent the Damper/BAS Interlock
condition.

1. Option 1: Install a normally closed (N.C.) BAS Interlock Circuit between TB1-3 and TB1-9 on PCB A2.

Refer to

Figure 6

.

2. Option 2: Install a jumper between TB1-3 and TB1-9 on PCB A2 according to

Figure 7

.

This method should be

used if a BAS Interlock Circuit will be added later in the installation.

3. Option 3: De-activate terminal TB1-3 by moving DIP switch S2-8 to the ON position (toward the enclosure door).

Refer to

Figure 8

. This solution is only suggested if a BAS Interlock Circuit will never be applied to the drive system

.

Figure 6

Figure 6 Option 1: Normally Closed (N.C.) Damper/BAS interlock Installation