Yaskawa CM059 User Manual

Page 2

Advertising
background image

Yaskawa Electric America, Inc. –

www.yaskawa.com

IG.G5HHP.13 Page 2 of 10

Date: 11/06/06 Rev: 06-11

‰

Set the CM059 DeviceNet Option Baud Rate

Set the Baud Rate for the CM059 DeviceNet Option to the network baud rate by setting DIP switches DR1 (1) and DR0 (2) as shown in the figure to the right. The baud rate
must match the baud rate of the DeviceNet master (PC/PLC/Scanner) in order for the connection to function properly.

‰

Set the CM059 DeviceNet Option MAC ID

Set the MAC ID of CM059 DeviceNet Option by setting DIP switches ADR 5 (3) through ADR 0 (8) as shown in the table below. Each device on the network must have a
unique MAC ID, typically between 3 and 62. Addresses 0 and 1 are usually reserved for DeviceNet masters, address 2 for diagnostic/monitoring equipment and address 63
for vendor specific functions in some systems. Check the network schematic to verify the MAC ID setting.

MAC ID

Sw

00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31

ADR 5 (3) 0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

ADR 4 (4) 0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

ADR 3 (5) 0

0

0

0

0

0

0

0

1

1

1

1

1

1

1

1

0

0

0

0

0

0

0

0

1

1

1

1

1

1

1

1

ADR 2 (6) 0

0

0

0

1

1

1

1

0

0

0

0

1

1

1

1

0

0

0

0

1

1

1

1

0

0

0

0

1

1

1

1

ADR 1 (7) 0

0

1

1

0

0

1

1

0

0

1

1

0

0

1

1

0

0

1

1

0

0

1

1

0

0

1

1

0

0

1

1

ADR 0 (8) 0

1

0

1

0

1

0

1

0

1

0

1

0

1

0

1

0

1

0

1

0

1

0

1

0

1

0

1

0

1

0

1

MAC ID

Sw

32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63

ADR 5 (3) 1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

ADR 4 (4) 0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

ADR 3 (5) 0

0

0

0

0

0

0

0

1

1

1

1

1

1

1

1

0

0

0

0

0

0

0

0

1

1

1

1

1

1

1

1

ADR 2 (6) 0

0

0

0

1

1

1

1

0

0

0

0

1

1

1

1

0

0

0

0

1

1

1

1

0

0

0

0

1

1

1

1

ADR 1 (7) 0

0

1

1

0

0

1

1

0

0

1

1

0

0

1

1

0

0

1

1

0

0

1

1

0

0

1

1

0

0

1

1

ADR 0 (8) 0

1

0

1

0

1

0

1

0

1

0

1

0

1

0

1

0

1

0

1

0

1

0

1

0

1

0

1

0

1

0

1

‰

Verify LED Status

Refer to the table on the following page for a complete listing of LED states.

LED Power-Up Sequence

LED

Color

Condition

PWR GREEN Steady

WD

RED

On for 0.25 sec

WD

NONE

Off for 0.25 sec

WD

GREEN Blink at 0.1ms interval

MS

GREEN On for 0.25 sec

MS

RED

On for 0.25 sec

MS

GREEN On for 0.25 sec

NS

GREEN On for 0.25 sec

NS

RED

On for 0.25 sec

LED normal operation Status

LED

Condition

PWR GREEN

MS GREEN

FLASH GREEN (no communication)

NS

REEN (communicating)

WD FLASH

GREEN

‰

Remove power from the drive and wait for the charge lamp to be completely
extinguished. Wait at least five additional minutes for the drive to be completely
discharged. Measure the DC bus voltage and verify that it is at a safe level.

‰

Reinstall all drive covers and the operator keypad.

‰

Apply power to the drive and wait for the power-up sequence to complete.

‰

Set parameters b1-01 and b1-02 to their appropriate values. Refer to the table to the
right for available b1-01 and b1-02 values.


Baud Rate

Sw

125kbps 250kbps

500kbps

N/A

DR1 (1)

0

0

1

1

DR0 (2)

0

1

0

1

Param

Function

Data

Description

Dflt

0 Digital

Operator

1 Terminals

2

Built-in Modbus RTU Terminals

b1-01

Reference

Source

Select

3

Option Card (CM059 DeviceNet
Option
)

1

0 Digital

Operator

1 Terminals

2

Built-in Modbus RTU Terminals

b1-02

Run

Command

Source

Select

3

Option Card (CM059 DeviceNet
Option
)

1

Advertising