Electrical installation 2 - 7, Important – Yaskawa P7 Drives User Manual

Page 7

Advertising
background image

Electrical Installation 2 - 7

4132

R/L1, S/L2, T/L3,

,

1, R1/L11, S1/L21, T1/L33

M10

154.8 to 197.5

(17.6 to 22.5)

N/A

3/0

× 2P

(80

× 2P)

600Vac

UL Approved

vinyl-sheathed

or equivalent

U/T1, V/T2, W/T3

N/A

2/0

× 2P

(70

× 2P)

3

M8

77.4 to 95.0

(8.8 to 10.8)

N/A

Application

Dependent

M12

276.2 to 344.8

(31.4 to 39.2)

N/A

4/0

(100)

r/

l

1,

s

200/

l

2

200,

s

400/

l

2

400

M4

11.4 to 12.3

(1.3 to 1.4)

N/A

16

(1.25)

4160

R/L1, S/L2, T/L3,

,

1, R1/L11, S1/L21, T1/L33

M12

276.2 to 344.8

(31.4 to 39.2)

N/A

4/0

× 2P

(100

× 2P)

U/T1, V/T2, W/T3

N/A

3/0

× 2P

(80

× 2P)

3

M8

77.4 to 95.0

(8.8 to 10.8)

N/A

Application

Dependent

M12

276.2 to 344.8

(31.4 to 39.2)

N/A

1/0

× 2P

(60

× 2P)

r/

l

1,

s

200/

l

2

200,

s

400/

l

2

400

M4

11.4 to 12.3

(1.3 to 1.4)

N/A

16

(1.25)

4185

R/L1, S/L2, T/L3,

U/T1, V/T2, W/T3, R1/L11, S1/L21, T1/L33

M16

693.9 to 867.4

(78.4 to 98.0)

N/A

300 x 2P

(150 x 2P)

, 1

N/A

600 X 2P

(325 X 2P)

3

N/A

Application

Dependent

N/A

3/0 x 2P

(80 x 2P)

r/

l

1,

s

200/

l

2

200,

s

400/

l

2

400

M4

11.4 to 12.3

(1.3 to 1.4)

N/A

16

(1.25)

4220

R/L1, S/L2, T/L3, R1/L11, S1/L21, T1/L33

M16

693.9 to 867.4

(78.4 to 98.0)

N/A

500 x 2P

(325 x 2P)

U/T1, V/T2, W/T3

N/A

400 x 2P

(200 x 2P)

, 1

N/A

250 X 4P

(125 X 4P)

3

N/A

Application

Dependent

N/A

250 x 2P

(125 x 2P)

r/

l

1,

s

200/

l

2

200,

s

400/

l

2

400

M4

11.4 to 12.3

(1.3 to 1.4)

N/A

16

(1.25)

4300

R/L1, S/L2, T/L3, R1/L11, S1/L21, T1/L33

M16

693.9 to 867.4

(78.4 to 98.0)

N/A

250 x 4P

(125 x 4P)

U/T1, V/T2, W/T3

N/A

4/0 x 4P

(100 x 4P)

, 1

N/A

400 X 4P

(200 X 4P)

3

N/A

Application

Dependent

N/A

250 x 2P

(125 x 2P)

r/

l

1,

s

200/

l

2

200,

s

400/

l

2

400

M4

11.4 to 12.3

(1.3 to 1.4)

N/A

16

(1.25)

*1 Wire size range provided for Drives using insulated screw-type terminal blocks. All other models require the use of UL listed connectors. Refer to Table 2.3.
*2 Recommended wire sizes are based on the AC drive normal duty (ND) current ratings and NEC Article 310 Table 310.16, 75 Degree Celsius copper or

equivalent.

IMPORTANT

Determine the wire size for the main circuit so that line voltage drop is within 2% of the rated voltage. Line

voltage drop is calculated as follows:

Line voltage drop (V) =

x wire resistance (

Ω/km) x wire length (m) x current (A) x 10

-3

Table 2.2 480Vac Wire Sizes and Connector Specifications (Continued)

Drive Model

CIMR-P7U

Terminal Symbol

Terminal

Screws

Clamping

Torque

lb. in.

(N•m)

Possible Wire

Sizes AWG

(mm

2

)

*

1

Recommended

Wire Size AWG

(mm

2

)

*2

Wire Type

3