Yaskawa Electric America, Inc –

www.yaskawa.com

IG.V7.25, Page 5 of 6

Date: 10/08/09, Rev: 09-10

16.

Remove power from the V7 drive and wait for the charge lamp to be
completely extinguished. Wait at least five additional minutes for the V7
to be completely discharged. Measure the DC bus voltage and verify
that it is at a safe level.




17.

Reinstall the operator keypad and terminal cover.

18.

Reapply power to the V7 drive.

19.

Set parameters n003 and n004 to their appropriate values.
Important Notes:

1. Note: A maximum of 10 simultaneous connections are allowed.
2. The Run Command and Frequency Reference may only be accessed

through UNIT ID 1. While the V7 drive is in remote Run mode, the
Run command must be continually refreshed within the configured
EF0 timeout value. If the Run command is not refreshed within the set
timeout period, an EF0 fault will occur. Refer to the appropriate V7
manual for information on EF0 and setting the appropriate V7
response. If a UNIT ID 1 connection is active, the NS/CON LED will
blink at approximately a 500ms cycle.

3. The TCP/IP connection must be refreshed within 60 seconds. If it is

not refreshed within 60 seconds, the connection will be closed.

4. This implementation of Modbus TCP/IP supports the following Modbus functions: 3 (read multiple registers), 6 (write single register), 16 (write multiple registers) and

23 (read/write multiple registers).

5. Refer to the appropriate programming or parameter access manual for a complete list of V7 parameters and registers available. A list of applicable manuals is available

at the end of this document.

Address Parameter Function

Data

Description

Default

0 Operator

Keypad

1 Terminal

Strip

2

Built-in Modbus RTU

103h n003

Operation

Method

Selection

3

Option Kit (V7 Modbus TCP/IP Option)

1

0

Operator Keypad Potentiometer

1

Operator Keypad

2

Voltage Reference (0-10VDC)

3

Current Reference (4-20mA)

4

Current Reference (0-20mA)

5

Pulse Train Reference

6

Built-in Modbus RTU

7

Multi-Function Analog Input (0-10VDC)

8

Multi-Function Analog Input (4-20mA)

104h n004

Reference

Selection

9

Option Kit (V7 Modbus TCP/IP Option)

2

0 0.01

Hz

1 0.1

%

2-39

RPM (Enter motor poles)

198h n152

Display

Scaling

40-3999 User

Setting

0

20.

Notes:

1.

It is strongly recommended that shielded CAT-5 cable be used. Verify that the shield is continuous to the drive and that it is grounded only at the drive end.

2.

DriveWizard version 6.1 or later with a custom database is required for DriveWizard to operate with this option. Install DriveWizard with the

“Custom” install option checked and the appropriate databases selected.

21. Registers Available via High-Speed Command Registers

Command Register access is designed to be used as part of the standard PLC I/O or scan table, where fast response is required. Other register values should be accessed via
individual messages, i.e. via an MSTR block. Addresses 0001h, 0002h and 0009h may be written while all other registers in the table below are read only. Addresses 0001h and
0002h may only be accessed through Unit ID 1 (see above). Please note that Modbus RTU has different command registers.

Address

Description

0h

Multi-Function Digital Input S1
(Forward Run)

1h

Multi-Function Digital Input S2
(Reverse Run)

2h

Multi-Function Digital Input S3

3h

Multi-Function Digital Input S4

4h

Multi-Function Digital Input S5

5h

Multi-Function Digital Input S6

6h

Multi-Function Digital Input S7

7h Reserved
8h

External Fault (EF0)

9h Fault

Reset

Ah-Dh Reserved

Eh

Fault Log Trace Clear

0001h

Digital

Input

Command

Fh External

Base

Block

0002h

Frequency Reference Command (Scaled by n152)

0h Terminals MA, MB, MC

1h Terminals P1, PC

0009h

Digital
Output

Command

2h Terminals P2, PC
0h During

Run

1h Zero

Speed

2h Reverse

Direction

3h During

Fault

Reset

4h Speed

Agree

5h Drive

Ready

6h Minor Fault (Alarm)
7h Major

Fault

8h OPE

Fault

9h Momentary Powerloss Ride Thru

Ah Local

Mode

Bh Digital Output Terminals MA, MB, MC
Ch Digital Output Terminals P1, PC
Dh Digital Output Terminals P2, PC

2000h

Status

Word

Eh-Fh Reserved

Address

Description

2001h

Output Frequency (U-02) (Scaled by n152)

2002h

Torque Monitor (U-08) (1%) (Open Loop Vector only)

2003h Reserved
2004h

Frequency Reference Monitor (U-02) (Scaled by n152)

2005h

Output Frequency (U-02) (Scaled by n152)

2006h

Output Current (U-03) (0.1A)

2007h

Pulse Input (Terminal RP) Value

2008h

DC Bus Voltage (U-05) (1VDC)

0h Reserved
1h

UV1 Main Circuit Undervoltage

2h

UV2 Control Power Undervoltage

3h Reserved
6h OC

Overcurrent

7h OV

Overvoltage

8h OH

Overheat

9h Reserved

Ah

OL1 Motor Overload

Bh OL2

Drive

Overload

Ch OL3

Overtorque

Detection

2009h

Error Signal 1

Dh-Fh Reserved

0h

EF3 External Fault S3

1h

EF4 External Fault S4

2h

EF5 External Fault S5

3h

EF6 External Fault S6

4h

EF7 External Fault S7

5h ~ Ch Reserved

Dh

oPA Operator Disconnected

200Ah

Error Signal 2

Eh ~ Fh Reserved

Address

Description

0h

CE Communications Fault

1h

BUS Option Error

2h ~ 5h Reserved

6h

EF0 Option External Error

8h UL3

Undertorque

Detection

9h ~ Eh Reserved

200Bh

Error Signal 3

Fh

Fxx Hardware Fault

200Ch Reserved

0h Terminal

S1

1h Terminal

S2

2h Terminal

S3

3h Terminal

S4

4h Terminal

S5

5h Terminal

S6

6h Terminal

S7

200Dh

Digital Input

Terminal

Status

7h ~ Fh Reserved

200Eh Analog Input (Terminal FR) Value (0.1VDC)
200Fh Reserved

2010h

Drive Software Number (U-10)

WARNING!

Dangerous voltages in excess of 400VDC (230V drives) or 800VDC
(460V drives) are present at the DC bus terminals of the drive.