1 Replacing CDBR Spec. B and C with CDBR Spec. D

YASKAWA PL.CDBR.01 CDBR - Product Transition Guide

5

‹

CDBR Terminal and Wire Gauge Cross-Reference

The size and designation of some terminals differs between the new CDBR braking unit and previous models. Refer to

Table 4

,

Table 5

, and

Table 6

for details.

Table 4 Main Circuit Terminals

Table 5 Control Circuit Terminals

Braking Unit Model CDBR-…………

B and C

D

B1

B2

Braking Unit

CDBR-…………B

Terminal

Function

Braking Unit

CDBR-…………D

Terminal

Function

1

Slave Input

IN1

Input the signal when using CDBR braking units in parallel.

2

IN2

3

Cooling Fin Overheat

Contact Output

MA, MB, MC

Relay output the signal when a fault occurs or when SB-SC is closed (default).
(Example: CDBR braking unit overheating, LKEB braking resistor unit short
circuit detection, external fault)

4

5

Master Output

OUT1

Output the signal when using CDBR braking units in parallel

6

OUT2

-

-

SB/SC

Enable/Disable contact input to disable the CDBR and activate MA-MB-MC
fault contact output.

-

-

EA/EB/EC

Relay output the signal when LKEB braking resistor unit short circuit or CDBR
braking unit fault is detected.
Wiring sequence should shut off power to the drive when the signal is output.