Yaskawa Varispeed-656 DC5 Converter User Manual

Page 16

Advertising
background image

VS-656DC5 User’s Manual

14 - 20

(Note) These parameters normally need not be changed.

L1-03

Output OL (OL2) Detection
Start Current

110

50~200%

N

B

L1-04

Operation Selection At Output
OL (OL2) Operation

1

0/1

N

B

0: Continue Running
1: BB Stop

L2-01

Operation Selection At
Momentary Power Loss

0

0/1

N

B

0: None
1: Momentary Power Loss Ride Through

L2-02

Momentary Power Loss Ride
Through Time

1.0

0.0~2.0sec

N

B

L2-05

Undervoltage Detection Level

380

300~420V

Y

A

Setting 1.5x at 600V

L3-02

Input OL (OL1) Operation Time

60.0

1.0~120.0s

N

-

L3-03

Input OL (OL1) Detection
Starting Current

110

50~200%

N

-

L3-04

Input OL (OL1) Operation
Selection

1

0/1

N

B

0: Continue Running 1: BB Stop

L5-01

No. Of Fault Retries

0

0~10

N

B

L5-02

Contact Operation Selection
During Fault Retry

0

0/1

N

B

0: Error output contact not operating

during retry

1: Error output contact operating during

retry

L7-01

Drive Side Torque Limit

150

0~300%

N

B

L7-02

Regenerative Side Torque Limit

150

0~300%

N

B

L8-02

Converter OH Pre-alarm Level

95

50~110deg

N

A

L8-03

Operation Selection After
Converter OH Pre-alarm

3

1, 3

N

A

0: Continue Running 1: BB Stop

O1-01

Monitor Mode Display Item
Selection

8

4~50

Y

B

O1-02

Monitor Item Selection at Power
ON

1

1~4

Y

B

1: Output Voltage Reference (U1-01)
2: Output Voltage Feedback (U1-02)
3: Output Current (U1-03)
4: Monitor selected in O1-01

O2-01

LOCAL/REMOTE Key
Selection

1

0/1

N

B

0: Disable REMOTE/LOCAL key
1: Enable REMOTE/LOCAL key

O2-02

Stop Key Enable Selection
During REMOTE Operation

0

0/1

N

B

0: Enabled when there is a RUN

command from the digital operator

1: Always enabled

O2-04

kVA Selection

*

00~FF

N

B

81: 400V 200kW

91: 600V 300kW

82: 400V 400kW

92: 600V 600kW

83: 400V 600kW

93: 600V 900kW

84: 400V 800kW

94: 600V 1200kW

O2-06

Digital Operator Disconnection
Detection Disabled/Enabled
Selection

0

0/1

N

A

0: Continue running even when digital

operator is disconnected

1: Inverter error when digital operator is

disconnected

O2-07

Elapsed Time Set

-

0~65535H

N

A

O2-08

Elapsed Time Selection

0

0/1

N

A

0: Power feed time is cumulative running

time

1: Running time is cumulative running

time

DC5 Parameter List (Continued)

Parameter

No.

Name

Initial

Value

Setting Range

Change

on the

Fly?

Access

Level

Notes