Supplemental Information - Standards Compliance

u

Factory Recommended Branch Circuit Protection

Yaskawa recommends installing one of the following types of branch circuit protection to maintain compliance with UL508C.

Semiconductor protective type fuses are preferred.
Branch circuit protection shall be provided by any of the following according to

Table 2

.

• Non-time Delay Class J, T, or CC fuses.
• Time Delay Class J, T, CC, or RK5 fuses.
• Semiconductor fuses.
• Molded Case Circuit Breakers (MCCB).

Table 2 Factory Recommended Drive Branch Circuit Protection

Drive Model

Non-time Delay

Fuse Rating (A)

<1>

Time Delay Fuses

Bussmann

Semiconductor

Fuse Part Number
(Fuse Ampere)

<4>

MCCB

<5>

Class J, T, or CC

Fuse Rating (A)

<2>

Class RK5

Fuse Rating (A)

<3>

Rating (A)

Minimum

Enclosure

Volume (in

3

)

200 V Class Single-Phase Drives

BA0001

6

3.5

4

FWH-25A14F (25)

15

600

BA0002

10

6

8

FWH-25A14F (25)

15

600

BA0003

20

10

15

FWH-60B (60)

15

600

BA0006

40

20

30

FWH-80B (80)

30

1152

BA0010

40

35

45

FWH-100B (100)

50

1152

BA0012

<6>

50

40

50

FWH-125B (125)

60

1152

BA0018

<6>

80

60

70

FWH-175B (175)

80

1152

200 V Class Three-Phase Drives

2A0001

3

1.5

2

FWH-25A14F (25)

15

600

2A0002

6

<7>

3

3

FWH-25A14F (25)

15

600

2A0004

15

<8>

6

8

FWH-25A14F (25)

15

600

2A0006

20

10

15

FWH-25A14F (25)

15

1152

2A0010

25

15

20

FWH-70B (70)

25

1152

2A0012

25

20

30

FWH-70B (70)

30

1152

2A0020

40

40

50

FWH-90B (90)

60

1152

2A0030

60

80

FWH-100B (100)

90

1152

2A0040

<6>

90

110

FWH-200B (200)

125

1152

2A0056

<6>

110

150

FWH-200B (200)

150

2560

2A0069

<6>

125

175

FWH-200B (200)

200

2560

400 V Class Three-Phase Drives

4A0001

3

2

2

FWH-40B (40)

15

1152

4A0002

6

3.5

3

FWH-40B (40)

15

1152

4A0004

15

<8>

7

8

FWH-50B (50)

15

1152

4A0005

20

<9>

10

10

FWH-70B (70)

15

1152

4A0007

25

<10>

12

15

FWH-70B (70)

20

1152

4A0009

25

15

20

FWH-90B (90)

20

1152

4A0011

30

20

30

FWH-90B (90)

35

1152

4A0018

<6>

35

45

FWH-80B (80)

50

1152

4A0023

<6>

40

50

FWH-100B (100)

60

1152

4A0031

<6>

60

80

FWH-125B (125)

90

1152

4A0038

<6>

70

90

FWH-200B (200)

110

1152

<1> Maximum 300% of drive input current rating for any Class J, T, or CC fuse except for models 2A0002, 2A0004, 4A0004, 4A0005, and 4A0007.
<2> Maximum 175% of drive input current rating for any Class J, T, or CC fuse.

2 Supplemental Information - Standards Compliance

YASKAWA ELECTRIC TOEP YAISUP 07A YASKAWA AC Drive - V1000 & J1000 Manual Supplement