<3> Maximum 225% of drive input current rating for any Class RK5 fuse.
<4> When using semiconductor fuses, Bussmann FWH are required for UL compliance.
<5> Maximum MCCB Rating is 15 A or 200% of drive input current rating, whichever is larger. MCCB voltage rating must be 600 Vac or greater.

Additionally, when using MCCBs for protection, the drive must be installed in a ventilated enclosure with minimum volume according the “Minimum
Enclosure Volume” column.

<6> Available for V1000 only.
<7> Model 2A0002 requires Mersen (Ferraz) part number A6T6 for compliance.
<8> Models 2A0004 and 4A0004 require Mersen (Ferraz) part number A6T15 for compliance.
<9> Model 4A0005 requires Mersen (Ferraz) part number A6T20 for compliance.
<10> Model 4A0007 requires Mersen (Ferraz) part number A6T25 for compliance.

2 Supplemental Information - Standards Compliance

6

YASKAWA ELECTRIC TOEP YAISUP 07A YASKAWA AC Drive - V1000 & J1000 Manual Supplement