Date: 07/01/04, Rev: 04-07

Page 4 of 6

TM.V7SW.052

4.2 DC Injection Multi-function Digital Input Command

• The DC Injection command will be active under the following conditions: the inverter is ready (i.e. not

in program mode or in a fault state), no run command is present, and the output frequency is less
than the Minimum Frequency (n016).

• The DC Injection Current Level is set by the standard parameter n089 (as a percentage of inverter

rated current).

• The DC Injection at Start and DC Injection at Stop parameters n090 and n091 have priority over the

external DC Injection command.

• Full range DC injection (n005 = 2) has priority over the external DC Injection command.

• The External Baseblock command has priority over the external DC Injection command.

• The RUN LED on the digital operator will be lit solid when the DC injection command is closed.



Run

Command

DC Injection

Command

Output

Frequency

DC Injection

DC Injection

10ms

Baseblock *

* To prevent the 10ms Baseblock at the end of deceleration, set the DC Injection Time at Stop (n090) to 0.1 sec.

Figure 2.0 Multi-function Input DC Injection Command Timing Chart