Yaskawa V7 Large HP User Manual

Page 3

Advertising
background image

Date: 07/01/04, Rev: 04-07

Page 3 of 5

TM.V7SW.032H

Additional Parameters:

No.

Memobus

No.

Parameter Description

Unit

Setting Range

Defaul

t

Access Level

Change

During

Run

n045

012DH

Ratio Numerator

-

1 ~ 9999

1

First function

Y

n046 012EH Ratio

Denominator

-

1 ~ 9999

1

First function

Y

n170

01AAH

PID Dancer Setpoint

Hz*

0.00 ~ 400.0Hz**

0.00

Fourth Function

Y


* Unit depends on the setting of parameter n035 (Display Unit of Frequency Reference).
** For settings greater than 99.99, only one decimal place will be displayed.


Parameters n045 and n046 apply a ratio to the winder frequency reference. By setting n170 to a nonzero
value, it becomes the PID setpoint.

Additional Reference Selection Setting:

Setting Description

10

Winder ratio reference


When n004 = 10, the inverter frequency reference will be given by the winder ratio reference.

Additional Memobus Register:

Memobus

No.

Parameter Description

Unit

0004H

Winder frequency reference

1 = 0.01Hz


This register is only accessible using a Memobus broadcast command (slave address 0), so no response
message will be sent to the master. Any word length data is considered valid data; if the post-ratio
reference is greater than n011 (max frequency), the commanded reference will be n011 (See Fig. 2).


Detailed Description of Functionality:

Ratio Function

When n004 = 10, the frequency reference is given by the Memobus broadcast register 0004H multiplied
by the ratio of n045 / n046.

n046

n045

0004H

register

Memobus

reference

Frequency

×

=


The calculation is updated each time a write to the register is made.

Fig. 2 – Block Diagram of Winder Ratio Frequency Reference


x

n040

Ratio Numerator

÷

n041

Ratio Denominator

Memobus broadcast

register 0004H

n011

Max Frequency

Frequency

reference

Upper/lower limit (n033/n034)

Jump frequencies (n083 - n085)

Minimum frequency (n016)

New write

to 0004H