Cable Loss Behavior 5-4
Stop
COMM FLT ENA (POINT 90) must be set to ‘On’. In this mode, CBL LOSS TMR (POINT 92) is set to the desired interval and 
parameter H5-04 is set to a value of 0,1 or 2. If the time between messages exceeds the timeout interval, the drive’s speed 
command, INPUT REF 1, (Point 60) is set to 0. The stopping method is determined by the setting of H5-04. An EF0 drive fault 
will be set. 
H5-04 = 0 selects Ramp to Stop. The deceleration time or the slope of the ramp is determined by the setting of drive
parameter C1-02.
H5-04 = 1 selects Coast to Stop. The drive does not attempt to control the rate of deceleration.
H5-04 = 2 selects Emergency or Fast Stop. The deceleration time is determined by the setting of drive parameter C1-09.
CAUTION
The behavior of the drive at cable loss is controlled by parameter H5-04. This drive parameter works 
with the points as described in the table above to determine how the drive will respond to a cable 
loss. If the cable loss fault is disabled, the drive will continue in its last state, if running the drive 
will continue to run at the last commanded frequency. 
Fault (EF0)
In this mode, CBL LOSS TMR (POINT 92) is set to the desired interval, COMM FLT ENA (POINT 90) or is set to ‘On’ and either 
CMD RUN.FWD (Point 22) or CMD RUN.REV (Point 24) is set to ‘On’. If the time between messages exceeds the timeout 
interval, an ‘EF0’ fault is declared and the drive stops. The stopping method is controlled by the setting of H5-04 and is described 
above. CBL LOSS FRQ (POINT 91) is ignored.