Wiring & cabling, Wiring and cabling, The network cable is the correct type – Yaskawa E7 Apogee FLN User Manual

Page 51: Troubleshooting a-7

Advertising
background image

Troubleshooting A-7

Wiring And Cabling

!

The network cable is the correct type

Table A.4 - APOGEE FLN Cable Specifications

Specification

Description

Cable Configuration

Twisted Shielded Pair

Gauge

18-20 AWG (Solid or Stranded)

Wire Lay

Minimum 6 twists per foot

Shields

100% foil with drain wire

NEC Type

UL Type CMP

Temperature 60

o

C or higher

Cable Lengths Are Within Specified Limits

Cable lengths cannot exceed 500 feet at 4800 baud.

The Network is Terminated Correctly

Each APOGEE FLN network segment must be terminated on both ends to eliminate signal reflections. It is recommended that the Siemens
Building Automation BLN Trunk Terminator (PN: 538-664) be used and that the network termination switch on the E7 drive, S1-1, be set
to OFF.

Shield Is Continuous And Both Ends Of The Shield Are Grounded

As each drive is daisy-chained to the next, twist together the shields of the adjoining cables. Do not connect the shield at each drive.
The continuous shield should then be single-point grounded at the field panel.

Cable Is Routed Correctly

Route the cable away from all power and high frequency lines. Routing within a separate conduit is preferred.