2 Output Voltage PID

YASKAWA TM.A1000SW.061 Output Voltage PID A1000 Custom Software Supplement

9

Table 6 Multi-Function Input Settings (H1-……)

Table 7 Multi-Function Output Settings (H3-……)

‹

Troubleshooting

Table 8 Fault

U7-03

0662h

Voltage Error
Voltage Error

Difference between the voltage setpoint (P1-02) and the voltage
feedback.

10V:100 Vac

0.1 Vac

– – – – – – Y

U7-04

0663h

Output Voltage PID Output
Voltage PID Out

Displays the contribution of the output voltage regulator.

10V:100 Vac

0.1 Vac

– – – – – – Y

U7-05

0664h

Output Current Voltage
Compensation Level
Iac Comp Voltage

Displays the contribution of the output current V compensation.

10V:100 Vac

0.1 Vac

– – – – – – Y

U7-06

0665h

Iq Voltage Compensation
Level
Iq Comp Voltage

Displays the contribution of the Iq Voltage compensation.

10V:100 Vac

0.1 Vac

– – – – – – Y

Setting

Description

19

PID Disable
Closed: Output Voltage PID is disabled.

30

PID Integral Reset
Closed: Output Voltage PID Integrator is reset to zero.

31

PID Integral Hold
Closed: Output Voltage PID Integrator is held at its present value.

Setting

Description

Analog input scaling

Control Method/

Access Level

20

Output Voltage Feedback
Output V Fdbk

Full scale: 10V = P1-07 Value

– – – – – – Y

21

Output Voltage Setpoint
V Setpoint

Full scale: 10V = P1-07 Value

– – – – – – Y

Fault Display

Description

Cause

Countermeasures

oPE12
Energy Save ON

The energy savings feature was enabled when the
output voltage PID was enabled.

Parameter b8-01 was set to "Enable" when
parameter P1-08 is set to "Enable" and control
method is V/f.

Set b8-01 = 0 or Set P1-08 = 0

Monitor No.

MEMOBUS/

Modbus

Address

Monitor Name

Digital Operator Display

Description

Analog output

scaling

Unit

Control Method/

Access Level