KACO Powador 3200 - 6600 User Manual

Page 39

Advertising
background image

EN

Configuration and Operation

Page 39

Operating Instructions for Powador 3200-6600_EN

Authorised electrician

Coun-

try-spec.

Settings

Menu

level

Display/

setting

Action in this menu/meaning

All countries

"

Set f_rise gradient.

"

Set f_fall gradient.

NOTE: Set gradients for power limitation with rising and

falling mains frequency in %/Hz. This percentage relates

to the nominal frequency of 50 Hz

"

Set f_act.

NOTE: Set the current shutdown frequency.

"

Set min f_deact.

"

Set max f_deact.

NOTE: Set shutdown frequency for the power limitation

with rising and falling mains frequency in Hz.

"

Set T_deact

NOTE: Set minimum period (1-1800 s) during which the

inverter must remain within one frequency range until

P(f) is deactivated.

All countries

1

2

3

3

Activate

or deactivate

password protec-

tion.

"

Activate password protection for mains parameter

setting.

NOTE: After activation, only read access is available to the

mains parameter settings.

All countries

1

2

3

3

Starting voltage

The inverter begins feed-in as soon as this PV voltage is

present.

"

Set the starting voltage.

All countries

1

2

3

3

Activate

SYM bus

The SYM bus must be activated in order to synchronise a

group of inverters.

"

Enter SYM bus CAN address (1-32)

"

Set SYM bus phase (none, L1, L2, L3)

"

Enter SYM bus asymmetry (< 4600 W (IT < 6000 W) up

to 100 W) setting in 100 W increments

"

Activate SYM bus test (check settings for plausibility)

IT-CEI021

1

2

3

3

Activate self-test

With an active self-test and feed-in operation, the switch-

off values for grid voltage and grid frequency and the

result of the test are displayed.

All countries

1

2

3

3

Internal

power

limitation

Power reduction is password-protected in some coun-

tries. Power is reduced in 10 W steps and is

limited to 50 % of the nominal unit power.

"

Set power limiting.

"

Password protection can be re-activated.

All countries

1

2

3

3

Set default power

Provides the option of maintaining the pre-configured

power limitation even in the event of a fault halting com-

munication.

"

Set power in xxxx / 1000 in ‰ (promille).

"

Set internal fall-back time to set default power if

external power reduction is not pending.