11.3 Troubleshooting

Fault

Cause

Rectification

The display is blank and the LEDs are not lighting up.

↻ Grid voltage not available.
�

Check whether the AC voltages are within the permitted

limits (see Technical Data).

�

Have the cables and fuses checked by a qualified electri-

cian.

�

If necessary, notify KACO service.

The device has shut off the PV system from the grid.

↻ The green "Relay connected" LED is off.

↻ The red "Fault" LED is illuminated.
1. Check the status and fault signals.
2. Determine the fault category:
�

Grid errors: wait for re-connection of the system.

Where necessary have the cables and fuses checked by an

electrician.

�

Internal fault: Notify KACO Service.

No access to settings on menu level 3.

↻ The device is password protected.
�

Enter the password.

�

If unknown: Notify KACO Service.