INPUT DC VOLTAGE Setting: The INPUT DC VOLTAGE setting is determined

by connecting two small pins with a small black plastic box (i.e., jumper). This

setting can be confi gured for 12, 24, or 48 VDC operation, which is determined

by the nominal DC voltage connected to Terminals 3 and 4 on the AGS.

For 12-volt DC operation, position the jumper on the bottom two pins.

For 24-volt DC operation, position the jumper on the middle two pins.

For 48-volt DC operation, position the jumper on the top two pins.

INPUT DC

VOLTAGE

Setting

12/24/48V

ON

4

3

2

1 13

4

2

ON

4
3

2
1

GEN

TYPE

Setting

RY1 RY2

RY3

Revision

Label

12/24/48V

Rev

##

(Default: 12V)

(Default: QD mode)

12 VDC Operation

(jumper on bottom

two pins)

**default setting**

24 VDC Operation

(jumper on middle

two pins)

48 VDC Operation

(jumper on top

two pins)

3.0 Setup

This section provides information on AGS settings and shows you how to

adjust these settings.

3.1 Internal

Settings

On the AGS controller, unscrew the four top screws and remove the plastic

cover to access an input DC voltage jumper and a 4-position DIP (Dual In-line

Package) switch. The INPUT DC VOLTAGE jumper position determines the con-

troller’s DC operating voltage. The DIP switch confi guration is used to select the

GEN TYPE which determines how the internal relays operate to automatically

start and stop the generator.

Figure 3-2, DC Voltage Settings

GEN TYPE Setting: The GEN TYPE setting is determined by a DIP switch,

which is actually 4 small switches that can be turned to the ON or OFF

position. The position of each of these 4 small switches is used to determine

the open and close timing sequence for the three internal AGS relays (RY1,

RY2 and RY3). The multiple positions of the DIP switch allow a wide range of

generator start/stop circuit confi gurations.
After determining the appropriate start/stop timing sequence for your

generator, use Table 3-1 to determine and set the correct GEN TYPE setting

for your generator’s start/stop requirements.
For examples and assistance in viewing which GEN TYPE setting is used for

specific generators, view the “ Generator Wiring Diagrams” under the Service

and Support area at www.magnumenergy.com.

Figure 3-1, Inside the AGS Controller