Setup, Table 3-1, gen type settings – Magnum Energy AGS Stand Alone (ME-AGS-S) User Manual

Page 21

Advertising
background image

© 2013 Magnum Energy, Inc.

18

Setup

ON

4

3

2

1

RY1

(N.O.)

RY2

(N.O.)

T1

T2

T3

RUN TIME

T3

RY1

(N.O.)

T1

T2

RUN TIME

RY2

(N.O.)

RY3

(N.O.)

T1

T2

RUN TIME

Portable

Mode

T1

=

2 sec.

T1

=

4 sec.

T2

=

10 sec.

2-Wire

Momentary

Mode

T1

=

2 sec.

T2

=

10 sec.

QD Mode

(default)

T1

=

20 sec.

T2

=

4 sec.

T3

=

10 sec.

3-Wire

Mode

T1

=

5 sec.

T2

=

2 sec.

T3

=

10 sec.

GEN

TYPE

Relay Timing/Operation (RY1/RY2/RY3)

Time

Period

2-Wire

Maintain

Mode

Generator: Quiet Diesel (Onan).

Generators: Marquis, Emerald, and Microquiet (Onan); Quiet Pack
Series (Generac).

Generator: EM Series with remote control (Honda).

Generators: RMY Series (Kohler); DynaGen Controllers

Generator: PT-ECU-63 controller with 2-wires (Powertech).

ON

4

3

2

1

ON

4

3

2

1

ON

4

3

2

1

T2

=

10 sec.

RY3

(N.O.)

RY3

(N.O.)

ON

4

3

2

1

RY1

(N.O.)

RY2

(N.O.)

T1

RUN TIME

T3

T2

T3

RY3

(N.O.)

RY1

(N.O.)

RY2

(N.O.)

T2

T1

T1

RUN TIME

RY1

(N.O.)

RY3

(N.O.)

RY2

(N.O.)

T3

=

5 sec.

T3

ON

4

3

2

1

T1

=

10 sec.

T2

=

14 sec.

5-Wire

Mode

Generators: BTDA / BEG (Westerbeke), 205-DS (Martin Diesel), NL-
673 (Northern Lights)

RY1

(N.O.)

RY2

(N.O.)

RY3

(N.O.)

T3

=

4 sec.

T4

=

25 sec.

T1

T2

T3

T1

T4

T1

RUN TIME

Table 3-1, GEN TYPE Settings