Input/Output Data

The QSNAP offers a standard data list (shown below) for default operation. The list is
configurable with data contained within Table 21 in Appendix A: QSNAP Parameters, using
the CH Studio application.

Input Data

Use Tables 10 and 11 when setting up the QSNAP input data.

Table 10: Input Assembly Data Definitions

Data

Description

Faulted/Trip

The motor controller is faulted or tripped

Warning

The motor controller has a warning of an impending trip

Running 1

The first motor controller is running

Running 2

The second motor controller is running

Permissive

The motor controller run/stop permissive

Resetting

Motor controller is in the process of resetting a fault

Thermal Capacity

% thermal capacity of the motor from 0 to 100%

RMS Average
Current

Average RMS current of the motor (0.000A)

Fault Codes and
Warning Codes

Valid fault and warning codes are:

0

No Fault

1

General Fault

2

Firmware Fault

3

Interdevice Communication Fault

4

Control Voltage Low Fault

5

Control Device Overtemperature Fault

6

Motor Phase Loss Fault

7

Motor Phase Imbalance Fault

8

Motor Ground Fault

9

Motor Underload Fault

10

Motor Overcurrent Fault

13

Motor Bypass Failure Fault

14

Motor Thermal Pile Fault

15

Control Device Test Fault

40000

Current Threshold Warning

40001

Underload Warning

40002

Control Device Overtemperature Warning

40003

Overload Warning

Advertising