4 administration, 5 network, 6 environment sensor – Eaton Electrical 34003991EN/EB User Manual

Page 11: 1 list of ports used

Advertising
background image

Network Management Card

– User Manual

34003991EN/EB

Page

11/118

1.3.4 Administration

Up to 35 workstations(in TCP connected mode) or up to 100(in UDP broadcasted mode) protected by Network

Shutdown Modules - Central or local configuration.

Up to 5 browsers connected at the same time (3 in SSL).

Minimum recommended browser versions: Internet Explorer 6.x / 7.0, Mozilla Firefox 1.5 / 2.0 / 3.0

E-mail sending configurable according to UPS alarms and transmission of a periodical report.

Control of UPS on/off switching via the HTML interface.

Adjustment and control of PowerShare outlets via the HTML interface, sequential starting of the installation and

optimisation of backup time by shutting down non-priority systems.

Automatic data and time adjustment via NTP server.

Protection by encrypted password.

Protection by secure SSL connection.

Saving of logs in the non-volatile memory.

Languages available: English/French/Spanish/German/Italian.

On-line help in English available for each page.

Card firmware updated via the network.

Card Mass settings via the network with the NMC tool.

1.3.5 Network

◗

Fast ETHERNET 10/100 Mbits compatibility with auto-negotiation on the RJ45 outlet.

1.3.5.1 List of ports used

◗

BootP, DHCP

UDP 68, 67

◗

HTML

TCP 80

◗

SSL

TCP 443

◗

NSM in connected mode

TCP 5000

◗

NSM in broadcasted

UDP 4679 and 4680

◗

SMTP

25

◗

NTP

123

◗

SNMP V1

161

◗

TRAP SNMP

162

1.3.6 Environment sensor

◗

Temperature measurement from 0 to 70 °C with +/- 1 °C accuracy.

◗

Measurement of humidity from 0 to 100 % with +/- 6 % accuracy.

◗

Min / max time-stamped function for temperature and humidity.

◗

Choice of temperature readings in Celsius or Fahrenheit.

◗

High and low thresholds, hysteresis and offset adjustable via Web interface.

◗

Possibility of notification of status changes by e-mail, SMS or SNMP trap.

◗

Position detection of 2 dry contacts (maximum sensor/contact distance: 20 m).

◗

Name and status of each configurable contact.

Advertising