4.4.4 Central shutdown configuration

Click on "Notified Applications" in the menu, then "Configuration".

This page is used to define either the "shutdown" or the "notification" settings used by the Network Shutdown

Modules that connect to Network Management Card. These settings are used by the Network Shutdown Modules if

they are in central-configuration mode or if their configuration is not valid.

Shutdown duration: the shutdown duration necessary to properly shutdown the computer.

Shutdown after: the time available to the user from the power failure until the launch of the shutoff sequence of the

UPS and equipment. This parameter is optional. Uncheck the box if you wish not to use this parameter.

Broadcast : Sends network notifications to the Administrators and Users groups on events declared in the server

hosting the NSM

If you wish to set up a new configuration for the Network Shutdown Modules already set to "central-configuration

mode", proceed as indicated below:

Change the Network Shutdown Module parameters in the "Notified Applications" page.

Click the "Save" button.

In this page, select the NSMs for which you want to apply the new configuration.

Press the "Remove" button.

The NSMs selected will disconnect then reconnect and use the new configuration.