3 installation in the ups – Eaton Electrical 34003991EN/EB User Manual

Page 15

Advertising
background image

Network Management Card

– User Manual

34003991EN/EB

Page

15/118

Ethernet port

LED

Colour

Activity

Description

ACT

Green

Off

Card not connected to the network.

On

Card connected to the network but

without activity

Flashing

Port is active in receiving /

transmission

100M

Orange

Off

Port operating at 10Mbits/s.

On

Port operating at 100Mbits/s.

Service port

LED

Colour

Activity

Description

UPS

Green

Off

Card startup in progress.

Data

On

Communication with UPS in

progress

Flashing

Normal operation.

Communication with the UPS is

operational

RS232

Orange

Off

Configuration menu is active

On

Normal operation. Configuration

menu is deactived

Flashing

Communication with the

Environment Sensor (option).

2.3 Installation in the UPS

The Network Management Card (66102) can be "hot" installed in all UPSs of the MGE Office Protection Systems or

Powerware range equipped with a Minislot without having to shut it down.

Remove the protective plastic cover from the Minislot

Note the card's MAC address prior to insertion

Insert and tighten the card's retaining screws

Connect the ETHERNET cable

Wait 2 min. the card is completely operational when the green UPS Data LED flashes continuously

Advertising