Wireless Sounder Instructions

6

Programming the sounder

Programming the wireless sounder consists of the following 3 steps:

1. Setting communication between the receiver and the sounder
2. Setting sounder parameters
3. Testing the sounder

Step 1: Sounder/Receiver Communication Set up

The sounder must identify itself to the system's receiver by writing its ID into the
system. Perform according to the following steps:

1. Set the receiver to the Write mode.

NOTE:

WisDom; Main engineer menu> 9) Devices > 2)Sounder > 1) Allocation > Select sounder> Choose
ODWS1

Agility: Main Engineer menu: 2) Radio Devices > 1) Allocation > 1) RF Allocation

LightSYS (V2.40 and above): Main Engineer menu: 7) Install > 2) WL Device > 2) Allocation > 1) By
RF > 4) Sounder

2. Select the sounder's ID.
3. Unpack the supplied batteries.
4. Insert two speaker batteries and three Radio batteries into the batteries holders.
5. After a squawk is heard and the sounder's strobe flashes you have 10 seconds to

press on the tamper switch for at least 3 seconds. If the sounder is successfully
recognized, the system will sound a confirmation beep and the sounder will initiate
a second squawk sound and the 2 LEDs on the sounder will flash for 3 seconds.

6. Repeat the process for other sounders in the system.

Step 2: Setting the Sounder Parameters

Each sounder can be defined with different sets of parameters. The following table
describes the list of parameters of the sounder.

NOTE:

For the specific programming location of each parameter refer to the system manuals.

Strobe Control

Defines the Strobe operation mode:

 Always Off: The strobe is deactivated
 Follow Bell (Default): The strobe is activated when the sounder bell is

triggered

 Follow Alarm: The strobe is activated when an alarm event occurs in the

system

Strobe Blink

Defines the number of times the strobe will flash per minute (Default 40 times per
minute). Strobe Blink options:

[1] 20 times per minute

[4] 50 times per minute

[2] 30 times per minute

[5] 60 times per minute

[3] 40 times per minute (Default)