Retrotec 5000 Blower Door with DM32 User Manual

Dm32 blower door quickguide

Advertising
background image

Water in the tube will result in erroneous readings.

DM32 Blower Door QuickGuide

Step 1:

Prepare the building

Refer to the Gauge QuickGuide and become completely

familiar with its operation before performing a test.

□

Fireplaces and stoves must be cold with doors

closed (cover ashes).

□

Close and lock outside doors and windows so they

don’t open during the test.

□

Open all interior doors leading to conditioned spaces.

□

Shut off HVAC, combustion appliances, exhaust fans,

dryers, A/C and furnaces. Ensure they will not come on

□

Turn gas hot water to Pilot.

□ Set up the Door Panel.

Refer to your “Door Panel QuickGuide”

□ Connect the short red tube to the red port on the

gauge.

□ Connect the yellow tube between yellow ports marked

“Ref B” on fan and gauge. If the fan has a green port

(“Input B”), connect the green tube.

□ Connect the Ethernet style Speed Control Cable to the

fan and gauge.

□ Pass the red tube through the Door Panel and toss

the end at least 5 feet away from the fan’s airstream.

Remove or cover

ashes.

Turn gas valve

to Pilot.

Close all windows

and outside doors.

□

Place gauge near fan, or attach gauge to Door Panel.

□

Install the fan blowing outdoors. Cover the fan.

□

Connect power cord between fan and a wall outlet.

Power light must be on.

Step 2:

Install the system

QG303 Page 1 of 4 rev-2015-05-12

www.retrotec.com Support: (888)330-1345 International: +1(604)732-0142 Made in Everson, WA USA

DM32 digital gauge

Cloth panel

Download the “Blower Door Operation Manual” and the

“Residential Pressure & Air Leakage Testing Manual” from

www.retrotec.com Read warnings.

Umbilical cable

Fan

300

5000

6000

Open

B8

B8

Advertising